The EDAS-1010T-1 Analog I/O Panel accommodates up to 8 analog I/O channels in any combination of inputs or outputs.
Conditioned and non-conditioned channels can be mixed on the panel. The panel accepts any of the 5B Series isolated signal conditioning blocks so isolation/conditioning can be performed on any of the channels.
On channels where isolation/conditioning is not desired, the 5B socket can be bypassed by inserting two jumpers.
The panel interfaces to a data acquisition system through a standard-density 50-pin connector. The panel also includes a 34-pin and 50-pin expansion connector to allow additional EDAS-1010T-1 and EDAS-1011T-1 panels to be cascaded.
[Multifunction EDAS 1000 Series Termination Diagram]
![]() |
The EDAS-1011T-1 Digital I/O Panel accommodates up to 8 digital I/O channels in any combination of inputs or outputs.
Conditioned and non-conditioned channels can be mixed on the panel. The panel accepts any of the PCI-1100 Series Digital Opto-Isolator blocks, and on channels where isolation is not desired, the opto-isolator socket can be bypassed by inserting two jumpers.
The panel interfaces to a data acquisition system through a standard-density 34-pin or 50-pin connector, and also includes a 34-pin expansion connector for cascading of additional EDAS-1011T-1 panels.
[Digital EDAS 1000 Series Termination Diagram]