(URL: http://lanpoint.com/.html)
|
The EDAS-2004M-1/-2/-3/-4 Digital Input Modules provide 16 channels each. Depending on the module version the nominal input levels are 5 V, 24 V, 120 V or 240 V. The 16 channels are arranged as two 8 bit ports, Port 0 and Port 1. The digital inputs have 500 V channel to channel isolation with one return per channel. The modules provides 1500 V input to output isolation.
Click here to request more information about the EDAS CE system
| Part Number | Input Voltage | US List* |
| EDAS-2004M-1 | 24 V | Price |
| EDAS-2004M-2 | 120 V | Price |
| EDAS-2004M-3 | 240 V | Price |
| EDAS-2004M-4 | 5 V | Price |
| Parameter | Conditions | Specifications | ||
|---|---|---|---|---|
| Digital Input | Opto Isolators | 16 Inputs | ||
| EDAS-2004-1, 24V
Levels |
Low
High |
0-3VAC/DC max
9-30VAC/DC max |
||
| EDAS-2004-1, 24V
Current |
Vin = 24V | 2 mA max | ||
| EDAS-2004-2, 120V
Levels |
Low
High |
0-20VAC/DC max
70-130VAC/DC max |
||
| EDAS-2004-2, 120V
Current |
Vin = 120V | 2 mA max | ||
| EDAS-2004-3, 240V
Levels |
Low
High |
0-40VAC/DC max
140-250VAC/DC max |
||
| EDAS-2004-3, 240V
Current |
Vin = 240V | 2 mA max | ||
| EDAS-2004-4, 5V
Levels |
Low
High |
0-1VAC/DC max
2-10VAC/DC max |
||
| EDAS-2004-4, 5V
Current |
Vin = 5V | 3 mA max | ||
| Turn-on Time
Turn-off Time |
6 mS min
35 mS max |
|||
| Isolation | Channel - Channel
Input to Output |
500V
1500V |
||
| Current Consumption | 5VDC | 500 mA max | ||
| Dimensions | Inches
mm |
4.55D x 5.9H x 1.74W
116D x 150H x 42W |
||
| Operating Temperature Range | 0 to 60° C* | |||
| *All specifications are typical at 25° C unless otherwise noted. | ||||
Copyright 1996-2008 Intelligent Instrumentation Inc.